  "schema_version": "1.0.0",
  "id": "super-tecnico-condensate-drain",
  "name": "Dimensionado preliminar de desagües de condensados",
  "status": "browser_engine_available_remote_execution_planned",
  "entry_point": "../../desagues-condensados.html",
  "engine": "../../assets/condensate-drain-engine.js",
  "input_order": "units_from_furthest_to_outlet",
  "inputs": [
    "units[].capacity_or_known_flow",
    "units[].manufacturer_connection_internal_mm",
    "units[].segment_length_m",
    "slope_percent"
  ],
  "outputs": [
    "cumulative_flow_by_segment_l_h",
    "recommended_internal_diameter_by_segment_mm",
    "fall_by_segment_cm",
    "warnings_and_assumptions"
  ],
  "method": {
    "estimated_condensate": "cooling_capacity_kw * latent_fraction * 3600 / 2450",
    "gravity_capacity": "Manning equation for a half-full circular smooth pipe, with only 25 percent used as design capacity",
    "diameter_series_internal_mm": [16, 20, 25, 32, 40, 50, 63, 75, 90, 110]
  },
  "limitations": [
    "Not a certificate or automatic proof of regulatory compliance",
    "The 25 percent usable-capacity factor is a conservative engineering reserve, not a statutory value",
    "Manufacturer drain connection is always a minimum",
    "Pumps, siphons, air breaks, cleaning access and local wastewater rules require project review",
    "Direct manufacturer or measured condensate flow should replace estimates"
  ],
  "future_integrations": ["frigorista_psychrometrics", "installation_floorplan", "regulation_search"]
}